Self-Supervised Learning for Soft-Constrained AC-OPF in Multiphase Distribution Systems
원문 초록
This paper presents a self-supervised learning framework for fast, soft-constrained AC optimal power flow (OPF) in unbalanced multiphase distribution systems. The soft AC-OPF objective balances operating cost, renewable energy curtailment, and penalties for violating operating limits. A neural network predicts distributed energy resource (DER) setpoints conditioned on operating conditions, switch configurations, and objective weights. The predicted setpoints are then processed through a DER projection and differentiable AC power flow to enforce device limits and network equalities. The framework is trained by directly minimizing the AC-OPF objective, without optimal-solution labels. Experiments on 123-, 240-, and 906-bus systems yield mean objective gaps of 0.32%, 0.92%, and 0.56%, respectively, relative to IPOPT, across wide operating ranges. Across these systems and the evaluated high-load/low-generation and low-load/high-generation scenarios, the largest mean gap is 1.04%, with mean speedups of 58-5272 times relative to IPOPT.